2016-04-26 17:55:28 | 2ND REVIEW: FBC 2014 MECHANICAL | | PERMIT #16031333 | | 4/26/16 | | | | 1) THE RE-SUBMITTED PLANS DO NOT INDICATE AN AIR SPACE | | FOR MAKEUP AIR FLOW THROUGH THE SIDEWALL LOUVER TO THE | | FRONT DOORS AND FILTERS OF THE SPRAY BOOTH- THE BOOTH | | IS STILL SHOWN DIRECTLY AGAINST THE WALL. THE SUBMITTED | | LETTER FROM FLORIDA FILTRATION & SPRAY BOOTH SERVICES | | INDICATING THAT AN 18" AIR SPACE EXISTS BETWEEN THE | | BOOTH AND THE WALL WAS NOT SIGNED BY THE DESIGN | | PROFESSIONAL OF RECORD. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|