Plan Review Notes For Permit 16031333 |
Permit Number |
16031333 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-31 08:37:44 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16031333 | | 3/31/16 | | | | 1) A REVISION TO THE SUBMITTED MANUFACTURERS'S | | SPECIFICATIONS MUST BE SUBMITTED TO SHOW THE MODIFIED | | BOOTH PANEL WITH THE NEW 48"X48" MAKE-UP AIR OPENING. | | THE SPECS MUST SHOW THE REQUIRED FIRE DAMPER AND AIR | | FILTRATION COMPONENTS, AND INSTALLATION DETAILS MUST BE | | PROVIDED TO SHOW HOW A CONTINUOUS AIR-TIGHT AND | | WEATHER-TIGHT OPENING FROM INSIDE THE BOOTH TO THE | | EXTERIOR OF THE BUILDING WILL BE CONSTRUCTED. | | 2) PROVIDE STRUCTURAL DRAWINGS FOR INSTALLATION OF THE | | 48"X48"" OPENING IN THE EXTERIOR WALL. | | 3) PROVIDE TWO COPIES OF A MIAMI-DADE NOA OR FL. | | PRODUCT APPROVAL FOR THE 48"X48" LOUVER REVIEWED AND | | APPROVED WITH SIGNATURE BY THE ENGINEER OF RECORD. | | 4) PROVIDE ENGINEERED STRUCTURAL DETAILS FOR | | INSTALLATION OF THE ROOF GUARDS. | | | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|