2016-04-04 10:10:52 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 16031333 |
| W. P. B. PERMIT: 15110492 |
| ADD: 6212 GEORGIA AVE. |
| CONT: FLORIDA FILTRATION |
| TEL: (561)582-5543 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W |
| * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2014 |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. APRIL 04/ 2016 |
| ACTION: DENIED |
| |
| 1) THE REVISION INDICATES THE PERSONNEL EXIT DOOR WAS |
| RELOCATED TO THE SOUTHEND OF THE BUILDING. LOUVER WAS |
| RELOCATED. PLEASE PROVIDE COMPLIANCE WITH: |
| 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 2014 104.9.1 USED |
| MATERIALS AND EQUIPMENT. THE USE OF USED, RECYCLED, OR |
| RECLAIMED MATERIALS WHICH MEET THE REQUIREMENTS OF THIS |
| CODE FOR NEW MATERIALS IS PERMITTED. USED EQUIPMENT AND |
| DEVICES SHALL NOT BE REUSED UNLESS APPROVED BY THE |
| BUILDING OFFICIAL. |
| |
| |
| 2014 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING |
| INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN, |
| REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF |
| THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE: |
| |
| 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| |
| 1.2. RISK CATEGORY. |
| |
| 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| |
| 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| |
| TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. |
| |
| 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| 2) NEW DOORS AND LOVERS WILL NEED TO COMPLY WITH: 2010 |
| FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| COMPONENTS & CLADDING. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (C) PANEL WALLS: WALL LOUVERS 48 X 48 INCH LOUVER. |
| |
| 3)107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| 4) IF USED EQUIPMENT INFORMATION IS TO BE SUBMITTED FOR |
| APPROVAL BY THE BUILDING OFFICAIL OR NEW MATERIALS THIS |
| IS A METAL FRAME AND EXTERIOR TYPE OF BUILDING. PLEASE |
| PROVIDE ENGINEERING AND FRAMING REQUIREMENTS FOR THE |
| NEW OPENINGS AS WELL AS ENGINEERING FOR THE NEW |
| GUARDRAIL FOR THE ROOF TOP. PROVIDE ENGINEERING |
| ATTACHMENTS FOR THE GUARDRAIL SYSTEM TO THE MAIN |
| WINDFORCE RESISTING SYSTEM. |
| |
| 107.2.4 EXTERIOR WALL ENVELOPE. CONSTRUCTION DOCUMENTS |
| FOR ALL BUILDINGS SHALL DESCRIBE THE EXTERIOR WALL |
| ENVELOPE IN SUFFICIENT DETAIL TO DETERMINE COMPLIANCE |
| WITH THIS CODE. THE CONSTRUCTION DOCUMENTS SHALL |
| PROVIDE DETAILS OF THE EXTERIOR WALL ENVELOPE AS |
| REQUIRED, PRODUCT APPROVALS AND OR SHOP DRAWINGS. |
| |
| |
| FBC-B 1607.8.1 HANDRAILS AND GUARDS. HANDRAILS AND |
| GUARDS SHALL BE DESIGNED TO RESIST A LINEAR LOAD OF 50 |
| POUNDS PER LINEAR FOOT (PLF) (0.73 KN/M) IN ACCORDANCE |
| WITH SECTION 4.5.1 OF ASCE 7. GLASS HANDRAIL ASSEMBLIES |
| AND GUARDS SHALL ALSO COMPLY WITH SECTION 2407. |
| |
| EXCEPTIONS: 2. IN GROUP F OCCUPANCY FOR AREAS THAT ARE |
| NOT ACCESSIBLE TO THE GENERAL PUBLIC AND THAT HAVE AN |
| OCCUPANT LOAD LESS THAN 50, THE MINIMUM LOAD SHALL BE |
| 20 POUNDS PER FOOT (0.29 KN/ M). |
| |
| FBC-B 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND |
| GUARDS SHALL ALSO BE DESIGNED TO RESIST A CONCENTRATED |
| LOAD OF 200 POUNDS (0.89 KN) IN ACCORDANCE WITH SECTION |
| 4.5.1 OF ASCE 7. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |