2016-05-06 07:35:37 | 2ND ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 | | COMMENTS: | | | | 1. PROVISO- SEPARATE PERMITS REQUIRED FOR LOW VOLTAGE | | AND FIRE ALARM FOR ROLL UP SHUTTER. FBC 107.3.5 | | 2. AS-BUILT TO REFLECT WHAT BRANCH CIRCUITS WHERE USED | | FOR THE NEW POWER RECEPTACLES. FBC 107.3.5 | | 3. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW | | SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|