Date |
Text |
2016-03-31 15:09:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1. SHEET A 1.0 - THE PROPOSED PROJECT SHALL MEET THE |
| REQUIREMENTS OF THE 5TH EDITION OF FLORIDA FIRE |
| PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA 1 |
| AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR |
| STANDARDS. |
| FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 13, 2010 EDITION. |
| FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 72, 2010 EDITION. |
| |
| 2. SHEET A 1.0 - THE NATURE OF THE REMODEL REQUIRES AN |
| EVALUATION OF THE FIRE ALARM AND SPRINKLER SYSTEM FOR |
| CODE COVERAGE AND COMPLIANCE. ANY REMOVAL AND/OR |
| CONSTRUCTION OF WALLS REQUIRE AN EVALUATION. |
| THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| CONSTRUCTION PERIOD. |
| ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| AND COMPLETE PROTECTION IS RETURNED. |
| |
| 3. SHEET A 1.0 - TWO NEW DOORS ARE INDICATED ON THE |
| REMODLED FIRE WALL. THE SUBMITTED PALNS DO NOT INDICATE |
| A DOOR OR HARDWARE SCHEDULE. THE NEW DOOR AND HARDWARE |
| SET SHALL COMPLY WITH THE REQUIRMENTS EQUAL TO THE FIRE |
| RATING OF THE WALL ASSEMBLY. |
| |
| 4. SHEET A 2.0 - THERE ARE NO EXITS SIGNS INDICATED. |
| PLEASE PROVIDE EXIT SIGNS ACCORDING TO THE LIFE SAFETY |
| PLAN. |
| |
| 5. SHEET A 2.0 - THERE IS A DIMENSION OF 1' 9" BETWEEN |
| OFFICE FURNITURE/EQUIPMENT THAT ISOF INSUFFICIENT WIDTH |
| FOR EXIT PATH EGRESS. PLEASE PROVIDE A MINIMUM |
| COMPLIANT WIDTH OF 36" PER NFPA 101, CHAPTER 7, MEANS |
| OF EGRESS. |
| |
| 6. SHEET A 2.0 - THE 1-HOUR WALL DRAWING DOES NOT HAVE |
| A U.L. LISTING NUMBER REFERENCE. PLEASE PROVIDE THE |
| LISTING NUMBER. |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |