2016-03-28 17:49:10REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - RISER DIAGRAM SHOWS NO DISCONNECTING MEANS OF THE
 ELECTRICAL SERVICE PLEASE LOCATE NEAREST POINT OF
 ENTRY. NEC 230.70 A1
 KEEP IN MIND ALL DISCONNECTS MUST BE GROUPED AND
 PROPERLY LABELED. NEC 230.72 A , NEC 408.4 B
  
 - GROUNDING DETAIL TO INCLUDE INTERSYSTEM BONDING
 TERMINAL. NEC 250.94
  
 - CLARIFY IF METER ENCLOSURE LUGS ARE RATED FOR DUAL
 WIRES ? ( ACCORDING TO DRAWING )