2016-03-28 17:49:10 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | | | - RISER DIAGRAM SHOWS NO DISCONNECTING MEANS OF THE | | ELECTRICAL SERVICE PLEASE LOCATE NEAREST POINT OF | | ENTRY. NEC 230.70 A1 | | KEEP IN MIND ALL DISCONNECTS MUST BE GROUPED AND | | PROPERLY LABELED. NEC 230.72 A , NEC 408.4 B | | | | - GROUNDING DETAIL TO INCLUDE INTERSYSTEM BONDING | | TERMINAL. NEC 250.94 | | | | - CLARIFY IF METER ENCLOSURE LUGS ARE RATED FOR DUAL | | WIRES ? ( ACCORDING TO DRAWING ) |
|