Plan Review Notes For Permit 16031303 |
Permit Number |
16031303 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-31 17:01:28 | 1ST REVIEW: FBC 2014 MECHANICAL | | REVISION PERMIT #16031303 | | PERMIT #16020244 | | 3/31/16 | | | | 1) SHEET M-1: INDICATE THE CFM SUPPLY FOR THE 12X8 | | DIFFUSERS IN THE CONFERENCE ROOM, AND THE 10X8 IN THE | | PM3 ROOM. | | 2) M-1: THE 8" FLEX DUCTS SUPPLYING AIR TO THE ALLEN | | AND PRIVATE OFFICE ROOMS NEED TO REMAIN SIZED AT 9" AS | | THE ORIGINAL PLAN INDICATED. | | 3) M-1: SHOW DOOR OPENINGS INTO THE KITCHENETTE, AND | | STORAGE-3 ROOMS. | | 4) A-1 & M-1: THE WOOD LOUVERED DOOR FOR STORAGE ROOM-3 | | IS NOT IN COMPLIANCE WITH SECTION C403.2.7.2 FBC-14 | | ENERGY CONSERVATION. PROVIDE A NON-COMBUSTIBLE DOOR. | | 5) THE PLANS DON'T CLEARLY SHOW HOW SUPPLY AIR IS BEING | | RETRUNED TO SYSTEM B: PLEASE CLARIFY. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|