2016-03-29 16:22:01(1) FIRE ALARM INSTALLATION SHALL COMPLY WITH NEC, NFPA
 70 AND 72. ALL FIRE PROTECTION EQUIPMENT SHALL REMAIN
 INSERVICE DURING ALL PHASES OF CONSTRUCTION AND
 INSTALLATION.
  
 (2) NFPA 90A-6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN
 AIR DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY BRANCH
 CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A CAPACITY
 GREATER THAN 944 L/SEC (2000 FT3/MIN) AT EACH STORY
 PRIOR TO THE CONNECTION TO A COMMON RETURN AND PRIOR TO
 ANY RECIRCULATION OR FRESH AIR INLET CONNECTION IN AIR
 RETURN SYSTEMS HAVING A CAPACITY GREATER THAN 7080
 L/SEC (15,000 FT3/MIN) AND SERVING MORE THAN ONE STORY.
  
 (3) NFPA 72-10.18.2.4, 2010 VERIFICATION OF COMPLIANT
 INSTALLATION. WHERE REQUIRED, COMPLIANCE OF THE
 COMPLETED INSTALLATION WITH THE REQUIREMENTS OF THIS
 CODE, AS IMPLEMENTED VIA THE REFERRING CODE(S),
 SPECIFICATIONS, AND/OR OTHER CRITERIA APPLICABLE TO THE
 SPECIFIC INSTALLATION, SHALL BE CERTIFIED BY A
 QUALIFIED AND IMPARTIAL THIRD-PARTY ORGANIZATION
 ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION.
  