Plan Review Notes For Permit 16031271 |
Permit Number |
16031271 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-31 12:09:34 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | | | PASSED WITH A PROVISO OF THE FOLLOWING ITEMS | | | | - ADD A SMOKE DETECTOR IN FRONT OF FACP. NFPA 72 10.15 | | , FBC 907 .4.1 | | | | - INCLUDE GENERAL NOTE STATING MECHANICAL PROTECTION | | REQUIRED AND RED MARKING LABELED " FIRE ALARM CIRCUIT " | | . NEC 760 , NFPA 72 10.5.5.2 |
|