Date |
Text |
2016-03-30 16:22:41 | ELECTRICAL REVIEW COMMENTS |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014, NFPA 70 2011 (NEC) |
| |
| CORRECTIONS REQUIRED: |
| 1. 1. REGARDLESS OF WHEN THE CONVERSION WAS COMPLETED, |
| IT IS BEING PERMITTED NOW AND THEREFORE SHALL COMPLY |
| WITH CURRENT NATIONAL ELECTRICAL CODE REQUIREMENTS. |
| (2011). |
| 2. IN ADDITION TO THE EXISTING OUTLETS INDICATED ON THE |
| DRAWING, YOU SHALL ADD THOSE MARKED IN RED TO COMPLY |
| WITH MINIMUM CODE REQUIREMENTS. MARKINGS ARE |
| APPROXIMATE, CONSULT WITH INSPECTOR IN THE FIELD FOR |
| ACCURATE REQUIREMENTS. |
| 3. OF THE NEW REQUIRED OUTLETS MARKED ON THE PLANS, |
| THOSE HIGHLIGHTED IN YELLOW SHALL BE GFCI PROTECTED FOR |
| THE KITCHEN COUNTERS AND BATHROOMS. |
| 4. THOSE OUTLETS HIGHLIGHTED IN GREEN SHALL BE IN |
| ADDITION TO GFCI PROTECTED, BE WEATHER RESISTANT AND |
| HAVE AN IN-USE TYPE COVER AS WELL. |
| 5. BATHROOM TO APT 1 REQUIRES AN EXHAUST FAN WHICH |
| SHOULD COME ON WITH THE LIGHTS. |
| 6. APT. 2 IS MISSING A WALL SWITCH ADJACENT TO THE MAIN |
| ENTRY FOR THE CEILING LIGHT. |
| 7. NEC 406.12 ALL RECEPTACLES IN A DWELLING SHALL BE |
| TAMPER RESISTANT. |
| 8. NEC 210.12, ARC-FAULT REQUIREMENTS AS PER NEC SHALL |
| BE COMPLIED WITH. |
| 9. NEC 240.24(B) REQUIRES THAT EACH TENANT HAVE ACCESS |
| TO THEIR PANEL AT ALL TIMES. THEREFORE, UNLESS EACH |
| TENANT HAS THEIR PANEL INSIDE THEIR UNIT AND YOU HAVE A |
| COMMON ELECTRICAL PANEL FOR BOTH UNITS, THE PANEL SHALL |
| BE IN A PLACE ACCESSIBLE TO BOTH TENANTS. |
| 10. NEC 408.4 YOU SHALL SUBMIT LOAD CALCS AND A PANEL |
| SCHEDULE |
| 11. NEC 215.5 YOU SHALL PROVIDE A RISER DIAGRAM SHOWING |
| CONDUCTOR SIZING AND INDICATE NUMBER AND LOCATION OF |
| EVERY PANEL. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |