Plan Review Notes
Plan Review Notes For Permit 16031241
Permit Number 16031241
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-30 16:22:41ELECTRICAL REVIEW COMMENTS
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014, NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. 1. REGARDLESS OF WHEN THE CONVERSION WAS COMPLETED,
 IT IS BEING PERMITTED NOW AND THEREFORE SHALL COMPLY
 WITH CURRENT NATIONAL ELECTRICAL CODE REQUIREMENTS.
 (2011).
 2. IN ADDITION TO THE EXISTING OUTLETS INDICATED ON THE
 DRAWING, YOU SHALL ADD THOSE MARKED IN RED TO COMPLY
 WITH MINIMUM CODE REQUIREMENTS. MARKINGS ARE
 APPROXIMATE, CONSULT WITH INSPECTOR IN THE FIELD FOR
 ACCURATE REQUIREMENTS.
 3. OF THE NEW REQUIRED OUTLETS MARKED ON THE PLANS,
 THOSE HIGHLIGHTED IN YELLOW SHALL BE GFCI PROTECTED FOR
 THE KITCHEN COUNTERS AND BATHROOMS.
 4. THOSE OUTLETS HIGHLIGHTED IN GREEN SHALL BE IN
 ADDITION TO GFCI PROTECTED, BE WEATHER RESISTANT AND
 HAVE AN IN-USE TYPE COVER AS WELL.
 5. BATHROOM TO APT 1 REQUIRES AN EXHAUST FAN WHICH
 SHOULD COME ON WITH THE LIGHTS.
 6. APT. 2 IS MISSING A WALL SWITCH ADJACENT TO THE MAIN
 ENTRY FOR THE CEILING LIGHT.
 7. NEC 406.12 ALL RECEPTACLES IN A DWELLING SHALL BE
 TAMPER RESISTANT.
 8. NEC 210.12, ARC-FAULT REQUIREMENTS AS PER NEC SHALL
 BE COMPLIED WITH.
 9. NEC 240.24(B) REQUIRES THAT EACH TENANT HAVE ACCESS
 TO THEIR PANEL AT ALL TIMES. THEREFORE, UNLESS EACH
 TENANT HAS THEIR PANEL INSIDE THEIR UNIT AND YOU HAVE A
 COMMON ELECTRICAL PANEL FOR BOTH UNITS, THE PANEL SHALL
 BE IN A PLACE ACCESSIBLE TO BOTH TENANTS.
 10. NEC 408.4 YOU SHALL SUBMIT LOAD CALCS AND A PANEL
 SCHEDULE
 11. NEC 215.5 YOU SHALL PROVIDE A RISER DIAGRAM SHOWING
 CONDUCTOR SIZING AND INDICATE NUMBER AND LOCATION OF
 EVERY PANEL.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  