2016-06-15 18:23:24 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | - SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE SECTIONS | | SECTIONS 314 & 315 , VERIFY BUILDING COMMENTS FOR | | REQUEST TO PROVIDE ALL THE LOCATIONS IN AREAS | | APPLICABLE ON THE FLOOR PLAN. | | | | - MEDIA ROOM IS A HABITABLE LIVING SPACE THEREFORE NEC | | 210.52(A) APPLIES AND RECEPTACLE SPACING IS REQUIRED AS | | WELL AS NEC 210.70 LIGHTING OULET REQUIRED. CLARIFY THE | | INTENT OF THE SPACE | | BECAUSE ON THE OTHER SHEETS ITS LABELED AS EXISTING | | ENCLOSED PORCH ? PLEASE REFERENCE BUILDING COMMENTS. |
|