2016-04-04 16:37:42CITY OF WEST PALM BEACH
 LOCAL AMENDMENTS TO THE
 FLORIDA BUILDING CODE (FBC) 2010
 CHAPTER 1 ADMINISTRATION
  
 107.2.1 - CONFIRM CFM QUANTITY OF AHU SPECIFIED ON
 PLANS. AS PER CARRIER AIR HANDLER (INDOOR BLOWER &
 EVAP) OWNERS MANUAL SPECIFICATIONS - AHU - FVC4 - 003
 MATCHED WITH A CONDENSER UNIT CAPACITY 024 THE MAXIMUM
 EFFECTIVE COOLING (HIGH SPEED) IS 700 CFM, (LOW SPEED)
 560 CFM.
  
 PLANS SUBMITTED SHOW 1050 CFM AT TOTAL 23100 BTU.
 PROVIDE MANUFACTURE SPECIFICATIONS CONFIRMING THIS.
  
  