Plan Review Notes For Permit 16031224 |
Permit Number |
16031224 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-28 13:53:05 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | | | | | - PLEASE ADD THE FOLLOWING ELECTRICAL NOTES TO BE | | COMPLIANT | | | | 1 AFCI PROTECTION REQUIRED PER NEC 210.12B ( E3902.13 ) | | 2 TAMPER RESISTANT RECEPTACLES REQUIRED PER NEC 406.11 | | ( E4002.14 ) | | 3 BOXES AT FAN OUTLETS SHALL BE LISTED FOR 70 LB. NEC | | 314.27C ( E3905.8 ) | | 4 CLOTHES CLOSET LIGHTS NEAR COMBUSTIBLE MATERIAL NEC | | 410.16 A,B,C ( E4003.12 ) | | 5 RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT,AS WELL | | AS IC RATED AND SEALED TO NOT COMPROMISE | | BUILDING THERMAL ENVELOPE. ( 2 CFM ) FBC-ER 404.1.1 / | | 402.4.4 | | | | - INCLUDE GROUNDING DETAIL AND METER ENCLOSURE IN RISER | | DIAGRAM. WPBA 107 | | - NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME | | POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET ( CHECK | | BUILDING COMMENTS FOR MEDIA ROOM. ) |
|