Plan Review Notes
Plan Review Notes For Permit 16031224
Permit Number 16031224
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-28 13:53:05REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
  
 - PLEASE ADD THE FOLLOWING ELECTRICAL NOTES TO BE
 COMPLIANT
  
 1 AFCI PROTECTION REQUIRED PER NEC 210.12B ( E3902.13 )
 2 TAMPER RESISTANT RECEPTACLES REQUIRED PER NEC 406.11
 ( E4002.14 )
 3 BOXES AT FAN OUTLETS SHALL BE LISTED FOR 70 LB. NEC
 314.27C ( E3905.8 )
 4 CLOTHES CLOSET LIGHTS NEAR COMBUSTIBLE MATERIAL NEC
 410.16 A,B,C ( E4003.12 )
 5 RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT,AS WELL
 AS IC RATED AND SEALED TO NOT COMPROMISE
 BUILDING THERMAL ENVELOPE. ( 2 CFM ) FBC-ER 404.1.1 /
 402.4.4
  
 - INCLUDE GROUNDING DETAIL AND METER ENCLOSURE IN RISER
 DIAGRAM. WPBA 107
 - NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET ( CHECK
 BUILDING COMMENTS FOR MEDIA ROOM. )