Plan Review Notes
Plan Review Notes For Permit 16031224
Permit Number 16031224
Review Stop B
Sequence Number 1
Notes
Date Text
2016-04-20 15:01:59RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE; FBC, 5TH EDITION (2014).
  
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 2- NEED TO SPECIFY ON PLANS CARBON MONOXIDE ALARMS
 WITHIN 10 FEET OF ALL BEDROOMS AS REQUIRED BY SEC. R315
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 4- EXISTING AND DEMOLITION PLAN ON SHEET 2 SHOWS
 EXISTING MEDIA ROOM. ACCORDING TO CITY RECORDS AND
 PROPERTY APPRAISER THIS ROOM IS AN UNFINISHED ENCLOSED
 PORCH NOT A LIVING SPACE. REVISE AS REQUIRED. THIS ROOM
 MAY BE CONVERTED TO A MEDIA ROOM AS SHOWN ON SHEET 4
 BUT NEEDS TO SHOW COMPLIANCE WITH THE ENERGY
 CALCULATIONS (WALLS AND CEILING INSULATION) AND WITH
 THE ELECTRICAL REQUIREMENTS ( SEE ELECTRICAL REVIEW
 COMMENTS). SEC. 102.2 CITY AMENDMENTS.
  
 5- FLOOR PLAN ON SHEET 4 SPECIFY EXISTING WINDOWS TO BE
 REPLACED. CLEARLY SPECIFY THE TYPE AND SIZE OF EXISTING
 BEDROOM WINDOWS AND TYPE AND SIZE OF PROPOSED BEDROOM
 WINDOWS TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. 704 OF FBC-EXISTING BUILDING, 5TH
 EDITION (2014). NOTE: THIS INCLUDES THE EXISTING
 BEDROOM THAT WAS LOCATED ON THE NORTH-EAST CORNER AND
 WAS RENAMED AS "OFFICE". THIS ROOM CAN BE USED AS
 OFFICE OR BEDROOM.
  
 6- WINDOW ON THE EXISTING BATHROOM WAS BLOCKED TO ALLOW
 FOR THE MASTER BEDROOM ADDITION. SHOW COMPLIANCE WITH
 THE BATHROOM VENTILATION REQUIRED BY SEC. R303.3 OF
 FBC-RESIDENTIAL. NOTE: SEE EXCEPTION ON SEC. R303.3.
  
 7- PROPOSED NEW FLOOR PLAN ON SHEET #4 SPECIFIES THE
 FINISH FLOOR AT THE NEW MEDIA ROOM TO BE RAISED TO
 MATCH EXISTING HOUSE FLOOR ELEVATION. SPECIFY THE NEW
 CEILING HEIGHT TO VERIFY COMPLIANCE WITH SEC. R305 OF
 FBC-RESIDENTIAL.
  
 8- SPECIFY SIZE OF ATTIC ACCESS LOCATED IN THE NEW
 MASTER BEDROOM WALK-IN-CLOSET TO VERIFY COMPLIANCE WITH
 SEC. R807 FBC-RESIDENTIAL.
  
 9- EXTERIOR ELEVATIONS SHOW ROOF PITCH OF 3:12 +/-.
 NEED TO SPECIFY 2 LAYERS OF UNDERLAYMENT AS REQUIRED BY
 SEC. R905.2.2 FBC-RESIDENTIAL.
  
 10- A) PROVIDE COMPLETE SPECIFICATION S FOR THE BEAMS
 TO BE INSTALLED ON THE NEW ENTRY PORCH. ROOF FRAMING
 PLAN DOESN'T PROVIDE ANY SPECIFICATION. SEC. R301
 FBC-RESIDENTIAL.
  
 B) CLARIFY CONNECTION OF ENTRY PORCH TO THE EXISTING
 WALL. ROOF FRAMING PLAN ON SHEET #5 SPECIFIES "BEAM
 CONNECTOR C. SEE DETAIL ON PG-7". THERE IS NO DETAIL ON
 PAGE 7. REVISE AS REQUIRED. CLEARLY SPECIFY CONNECTOR
 AT THE END OF THE BEAM. SEC. R301 FBC-RESIDENTIAL.
  
 11- ROOF SHEATHING SPECIFICATIONS SHOWN ON NAILING
 DETAIL ON SHEET #8, TYPICAL WALL SECTION ON SHEET #9
 AND ROOF SHEATHING NOTES ON SHEET #10 DON'T MATCH
 SPECIFICATIONS SHOWN ON FASTENER SCHEDULE ON SHEET #5.
 REVISE AS REQUIRED TO MATCH. NOTE: SEC. R803.2.3.1
 FBC-RESIDENTIAL REQUIRES 8D RING SHANK NAILS MIN.
  
 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF SHINGLES SPECIFIED ON PLANS.
  
 B) WINDOWS MULLIONS AS SPECIFIED ON PLANS. AND, CLEARLY
 IDENTIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 ENGINEER CALCULATED DESIGN PRESSURES.
  
 C) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 D) GARAGE DOOR AS SHOWN ON PLANS (IF IS GOING TO BE
 REPLACED).
  
 E) ENTRY DOOR AS SHOWN ON PLANS.
  
 13- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (NOTE:
 INCLUDING THE ONES THAT WERE ALREADY SUBMITTED) AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 14- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $100,000. THE
 PERMIT FEE BALANCE IS $2298.86.
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON'T STAPLE OLD DRAWINGS TO NEW SET OF
 PLANS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]