Plan Review Notes For Permit 16031120 |
Permit Number |
16031120 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-29 08:36:46 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 | | COMMENTS: | | | | 1. SEE FBC RES 314 SMOKE ALARM REQUIREMENTS PER | | ALTERATION. PROVIDE SMOKE DETECTORS TO COMPLY AT THE | | EXTERIOR OF BEDROOM #3 ENTRANCE. | | 2. SHOW A DISCONNECT SWITCH FOR THE NEW GAS WATER | | HEATER. FBC RES E4101.5 | | 3. PROVIDE DATA CUT SHEET FOR THE NEW GAS WATER HEATER | | TO VERIFY RATINGS. FBC 107.3.5 | | 4. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW | | SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|