Plan Review Notes For Permit 16031116 |
Permit Number |
16031116 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-04-04 06:26:50 | 1) R403.9.1.1 GAS AND OIL-FIRED POOL AND SPA HEATERS. | | ALL GAS- AND OIL-FIRED POOL AND SPA HEATERS SHALL HAVE | | A MINIMUM THERMAL EFFICIENCY OF 82 PERCENT FOR HEATERS | | MANUFACTURED ON OR AFTER APRIL 16, 2013 WHEN TESTED IN | | ACCORDANCE WITH ANSI Z 21.56. POOL HEATERS FIRED BY | | NATURAL OR LP GAS SHALL NOT HAVE CONTINUOUSLY BURNING | | PILOT LIGHTS. PROVIDE DOCUMENTATION THAT THE POOL | | HEATER COMPLIES WITH THIS CODE SECTION. | | 2) R403.9.2 TIME SWITCHES. | | TIME SWITCHES OR OTHER CONTROL METHOD THAT CAN | | AUTOMATICALLY TURN OFF AND ON HEATERS AND PUMPS | | ACCORDING TO A PRESET SCHEDULE SHALL BE INSTALLED ON | | ALL HEATERS AND PUMPS. HEATERS, PUMPS AND MOTORS THAT | | HAVE BUILT IN TIMERS SHALL BE DEEMED IN COMPLIANCE WITH | | THIS REQUIREMENT. THE PLANS DO NOT SHOW THE TIME | | SWITCH. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | | | | | |
|