2016-03-29 06:56:25INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE SHOW ON DRAWING A NOTE INDICATING THE
 RECEPTACLE OUTLETS REQUIRED FOR WALL SPACE TO ENSURE
 THAT ALL WALL RECONFIGURED COMPLIES WITH FBC RES- SEC
 E39012.1 AND 2.2
 2. PROVIDE A NOTE TO COMPLY WITH AFCI PROTECTION FOR
 BRANCH CIRCUITS IF NEW BRANCH IS EXTENDED FROM PANEL
 BOARD AND TAMPER RESISTANT RECEPTACLE PER FBC RES- SEC
 E3902.12 AND E4002.14
 3. SEE FBC RES 314 SMOKE ALARM REQUIREMENTS PER
 ALTERATION. PROVIDE SMOKE DETECTORS TO COMPLY AT THE
 GUEST BEDROOM AND AT THE ENTRANCE TO ROOMS.
 4. SHOW THE NEW LOCATION OF ELECTRICAL PANEL THAT WAS
 RELOCATED DUE TO WALL DEMO. FBC 107.3.5
 5. LABEL ALL RECEPTACLES IN BATHROOM AREA TO GFCI
 PROTECTED. FBC RES E3902.1
 6. 75% OF LAMP TO BE HIGH EFFICACY LAMPS PER FBC EC
 404.1- A NOTE WILL SUFFICE.
 7. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL
 FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  