Plan Review Notes For Permit 16031101 |
Permit Number |
16031101 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-24 14:27:00 | | | 1ST REVIEW: FBC 2014 BUILDING | | PERMIT #16031101 | | 3/24/16 | | | | 1) THE CALULATED PRESSURES FOR ZONE 3 AT -56.3 ARE TOO | | LOW BASED ON TABLE 301.2(2) FBC-14 RESIDENTIAL, AND | | FIGURE 30.4-2.A ASCE 7- 10 WHICH INDICATES THE PARAPET | | SHALL BE MINIMUM 3' HIGH FOR ZONE 3 TO BE TREATED AS | | ZONE 2. PLEASE REVISE THE CALCULATIONS AND ENHANCED | | NAILING SPECIFICATIONS. | | 2) INDICATE ON THE APPLICATION HOW MANY SQUARE FEET OF | | FLAT ROOF AND HOW MANY SQUARE FEET OF SLOPED. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|