Plan Review Notes
Plan Review Notes For Permit 16031092
Permit Number 16031092
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-25 06:45:02INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. INSUFFICIENT INFORMATION PROVIDED FOR DESCRIPTION OF
 INSTALLATION. FBC 107.3.5
 2. CLARIFY AMOUNT OF TANK-LESS WATER HEATERS BEING
 INSTALLED. APPLICATION SAYS 8, ONLY 5 SHOWN DRAWINGS
 3. PROVIDE CUT SHEETS FOR UNITS. ARE THE UNITS
 INSTALLED OUTDOORS OR INDOOR, STATE LOCATION WITHIN
 CONDO. FBC 107.3.5
 4. LABEL PANEL BOARD LOCATION WITHIN CONDO FOR
 REFERENCE. FBC 107.3.5
 5. BRANCH CIRCUITS TO BE IDENTIFIED POWERING UNITS. NEC
 408.4
 6. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW
 SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS.
  
  
  