Plan Review Notes For Permit 16031067 |
Permit Number |
16031067 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-24 11:26:33 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | | | - PROVIDE EXISTING DWELLING UNIT LOAD CALCULATIONS WBA | | 107.3.5.3, GROUNDING DETAIL ON RISER DIAGRAM TO INCLUDE | | GROUNDING ELECTRODE SIZE NEC 250.66 AND INTERSYSTEM | | BONDING TERMINAL STRIP NEC 250.94 | | | | - PROVIDE GENERAL ELECTRICAL NOTES STATING NEC 300.5 | | PROTECTION FROM PHYSICAL DAMAGE EMERGING FROM GRADE ( | | PVC SCH 80 ) , WARNING RIBBON PLACED OVER TRENCH, AND | | RACEWAY SEAL FOR SERVICE CONDUCTORS. |
|