Plan Review Notes
Plan Review Notes For Permit 16031067
Permit Number 16031067
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-24 11:26:33REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - PROVIDE EXISTING DWELLING UNIT LOAD CALCULATIONS WBA
 107.3.5.3, GROUNDING DETAIL ON RISER DIAGRAM TO INCLUDE
 GROUNDING ELECTRODE SIZE NEC 250.66 AND INTERSYSTEM
 BONDING TERMINAL STRIP NEC 250.94
  
 - PROVIDE GENERAL ELECTRICAL NOTES STATING NEC 300.5
 PROTECTION FROM PHYSICAL DAMAGE EMERGING FROM GRADE (
 PVC SCH 80 ) , WARNING RIBBON PLACED OVER TRENCH, AND
 RACEWAY SEAL FOR SERVICE CONDUCTORS.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved