2016-05-11 09:19:083RD ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PROVISO TO PROVIDE AS-BUILT TO REFLECT UPDATED
 GOVERNING CODES AS STATED ABOVE AND ITEMS LISTED BELOW.
 2. SHOW GROUNDING ELECTRODE CONDUCTOR SIZE AT THE
 SERVICE PER SERVICE CHANGE. #2 GEC PER NEC 250.66
 TABLE.
 3. PROVIDE AN INTERSYSTEM BONDING CONNECTION. NEC
 250.94
 4. LABEL MAINS PER NEC 230.2 FOR ALL 100A BREAKERS
 SHOWN AT THE METER GANG BOX. EXAMPLE MAIN #1 OF 4, 2 OF
 4, ETC.
 5. PER FBC RES 315- PROVIDE SD/CO MONOXIDE DETECTORS ON
 THE EXTERIOR OF ROOMS.
 6. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  