Plan Review Notes For Permit 16030881 |
Permit Number |
16030881 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-04-04 18:02:54 | ELECTRICAL REVIEW COMMENTS | | REVIEWED FOR COMPLIANCE WITH: | | 2010 FBC & 2008 NEC | | | | CORRECTIONS REQUIRED: | | 1. THIS IS A LEVEL 2 ALTERATION OF AN R2 OCCUPANCY. | | 2. HOW DID THE ELECTRICAL GO FROM WHAT WAS PRESENTED ON | | THE INITIAL PLAN APPROVED ON 4/9/15 TO THE PLAN | | SUBMITTED ON 3/21/16. THE INITIAL PLANS SHOW THE | | ELECTRIC PANEL INSIDE THE UNIT AND THE NEW ONE HAS THE | | PANEL IN THE ELECTRIC ROOM. | | 3. DO ALL OF THE UNITS HAVE GAS OR ELECTRIC COOKING | | APPLIANCES. IF ELECTRIC, THE RESPECTIVE LOAD SHALL | | APPEAR ON THE LOAD CALCS. | | 4. DOES EACH UNIT HAVE AN INDEPENDENT WATER HEATER OR | | IS THERE A COMMON UNIT. THE SAME ARISES, ARE THEY GAS | | OR ELECTRIC. IF ELECTRIC THE LOAD SHALL APPEAR ON THE | | LOAD CALCS. | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | GREATLY APPRECIATED. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU, | | MIKE ALBARRAN | | ELECTRICAL PLANS EXAMINER | | PH: 561-805-6746 | | EMAIL: [email protected] | | |
|