Plan Review Notes For Permit 16030848 |
Permit Number |
16030848 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-24 09:52:31 | 1) CLEARLY SHOW THE DISTANCE OF THE GENERATOR FROM THE | | CLOSEST EXTERIOR WALL OF THE RESIDENCE. COMPLY WITH | | NFPA 37, SEC.4.1.4. | | 2) SUBMIT INSTALLATION SHEETS FOR THE GAS REGULATORS. | | REGULATORS SHALL BE APPROVED FOR THE APPLICATION. | | REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING | | SHALL BE APPROVED FOR OUTDOOR INSTALLATION. THEY SHALL | | ALSO BE APPROVED TO BE INSTALLED IN A VERTICAL | | POSITION. 2014 FUEL GAS CODE SEC.410.1. | | 3) SUBMIT COMPLETE MANUFACTURER SPECS FOR THE POOL | | HEATERS, FIREPLACE, BBBQ GRILL. ALL APPLIANCES / | | EQUIPMENT SHALL BE LISTED AND LABELED. FGC SEC.301.3. | | 4) SHOW THE TYPE OF PIPE MATERIAL AND THE SIZE OF THE | | PIPE FOR THE GAS TORCHES THAT IS DOWNSTREAM OF THE | | REGUATOR. COMPLY WITH THE SUBMITTED GAS SIZING TABLE | | FOR LOW PRESSURE. | | 5) SHOW THE TYPE OF PIPE MATERIAL AND THE SIZE OF THE | | PIPE IMMEDIATELY DOWNSTREAM OF THE GAS METER.FBC | | 107.2.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|