2016-04-01 10:09:25 | 1ST REVIEW: FBC 2014 5TH ED |
| CHRISTOPHER S. THROOP, C.B.O. |
| BLDG. PLANS EXAMINER ? PX3169 |
| (561) 805-6718 |
| [email protected] |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| |
| 1. PROVIDE SITE PLAN INDICATIING LOCATION OF WORK. |
| 2. IDENTIFY TYPE OF BLDG. AND OCCUPANCY. |
| 3. IDENTIFY TYPE OF CONSTRUCTION. |
| 4. STATE GOVERNING CODES. |
| 5. PROVIDE ROOF FRAMING PLAN. |
| 6. PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOF SYSTEM. |
| 7. PROVIDE WIND SPEED DESIGN LOAD CALC'S. |
| 8. OWNER AND CONTRACTOR TO SIGN APPLICATION. |
| 9. NOTICE OF COMMENCEMENT REQUIRED. |
| |
| FBC 107.3.5.3 ? PROVIDE A SITE PLAN TO DEMONSTRATE |
| SETBACKS AND BUILDING SEPARATION. |
| |
| FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION |
| PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL |
| FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING |
| DIMENSIONS; AND ALL EXTERIOR ELEVATIONS: |
| |
| FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY |
| FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING, |
| WINDOW, AND DOOR SUBMITTALS. |
| |
| FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN |
| PRESSURES PURSUANT TO FBC-CHAPTER 16 |
| 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| 2. RISK CATEGORY. |
| 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| |
| FBC EXISTING BUILDINGS - 611.1.1 - NOT MORE THAN 25 |
| PERCENT OF THE TOTAL ROOF AREA OR ROOF SECTION OF ANY |
| EXISTING BUILDING OR STRUCTURE SHALL BE REPAIRED, |
| REPLACED OR RECOVERED IN ANY 12 MONTH PERIOD UNLESS THE |
| ENTIRE ROOFING SYSTEM OR ROOF SECTION CONFORMS TO |
| REQUIREMENTS OF THIS CODE. |
| |
| PER THE MINIMUM PLAN REVIEW REQUIREMENTS FOUND IN FBC |
| 107, YOU MUST DECLARE THE CODE REFERENCE AND LEVEL OF |
| WORK. FOR YOUR CONVENIENCE, THE APPLICABLE CODE IS: THE |
| FBC 2014 5TH ED EXISTING BUILDING. IT SEEMS THE LEVEL |
| OF WORK IS EITHER A REPAIR OR MORE LIKELY AN ALTERATION |
| LEVEL I. PLEASE SEE SECTIONS 502 & 503 BELOW SO YOU MAY |
| MAKE A DETERMINATION. |
| SECTION 502 REPAIRS |
| |
| PLEASE ALSO INDICATE THE OCCUPANCY CLASSIFICATION AND |
| TYPE OF CONSTRUCTION OF THE BUILDING AS DEFINED IN FBC |
| CHAPTERS 3 & 6. |
| |
| |
| |
| |
| |