Plan Review Notes For Permit 16030791 |
Permit Number |
16030791 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-21 08:41:19 | | | APPLICABLE CODES IN EFFECT: | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. ELECTRICAL SHEET- PLEASE REFLECT CURRENT BUILDING | | CODES. FLORIDA BUILDING CODE 2014 5TH EDITION FAMILY, | | NEC 2011. | | 2. PLEASE CLARIFY ELECTRICAL SCOPE AND LABEL PLANS | | ACCORDINGLY. SHOW THE LOCATION OF NEW SERVICE AND A/C | | FBC 107.3.5 | | 3. PROVIDE A ONE-LINE RISER DIAGRAM REFLECTING ALL | | PERTINENT INFO. FOR EXAMPLE SERVICE CONDUCTOR SIZE, | | FEEDER CONDUCTOR SIZE, CONDUIT SIZE, EQUIPMENT RATINGS, | | GROUNDING ELECTRODE CONDUCTOR ARRANGEMENT ETC. FBC | | 107.3.5 | | 4. PROVIDE ALL A/C INFO AS WELL, SHOW DISCONNECT, WIRE | | SIZE ETC. SHOW THAT THERE IS A RECEPTACLE WITHIN 25FT | | TO SERVICE UNIT. FBC RES E3901.12 | | 5. ELECTRICAL CONTRACTOR TO SIGN AND NOTARIZED | | SIGNATURE ON DRAWINGS IF NO DESIGNER OF RECORD IS SHOWN | | FOR THIS PROJECT. ELECTRICAL PERMIT REQUIRED | | 6. SHOW THE SMOKE DETECTORS LAYOUT PER FBC RES 314 | | REQUIREMENTS | | 7. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL | | FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD | | YOU HAVE ANY QUESTIONS OR CONCERNS. | | | | | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | | | |
|