Plan Review Notes
Plan Review Notes For Permit 16030791
Permit Number 16030791
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-21 08:41:19 
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. ELECTRICAL SHEET- PLEASE REFLECT CURRENT BUILDING
 CODES. FLORIDA BUILDING CODE 2014 5TH EDITION FAMILY,
 NEC 2011.
 2. PLEASE CLARIFY ELECTRICAL SCOPE AND LABEL PLANS
 ACCORDINGLY. SHOW THE LOCATION OF NEW SERVICE AND A/C
 FBC 107.3.5
 3. PROVIDE A ONE-LINE RISER DIAGRAM REFLECTING ALL
 PERTINENT INFO. FOR EXAMPLE SERVICE CONDUCTOR SIZE,
 FEEDER CONDUCTOR SIZE, CONDUIT SIZE, EQUIPMENT RATINGS,
 GROUNDING ELECTRODE CONDUCTOR ARRANGEMENT ETC. FBC
 107.3.5
 4. PROVIDE ALL A/C INFO AS WELL, SHOW DISCONNECT, WIRE
 SIZE ETC. SHOW THAT THERE IS A RECEPTACLE WITHIN 25FT
 TO SERVICE UNIT. FBC RES E3901.12
 5. ELECTRICAL CONTRACTOR TO SIGN AND NOTARIZED
 SIGNATURE ON DRAWINGS IF NO DESIGNER OF RECORD IS SHOWN
 FOR THIS PROJECT. ELECTRICAL PERMIT REQUIRED
 6. SHOW THE SMOKE DETECTORS LAYOUT PER FBC RES 314
 REQUIREMENTS
 7. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL
 FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  