2016-03-21 08:21:03INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. ELECTRICAL SHEET- PLEASE UPDATE ALL REFERENCES TO
 REFLECT CURRENT BUILDING CODES. FLORIDA BUILDING CODE
 2014 5TH EDITION FAMILY, NEC 2011.
 2.PLEASE CLARIFY ELECTRICAL SCOPE AND LABEL PLANS
 ACCORDINGLY. LABEL NEW OR EXISTING FOR EXAMPLE INTERIOR
 DEVICES. FBC 107.3.5
 3.ELECTRICAL CONTRACTOR TO SIGN AND NOTARIZED SIGNATURE
 ON DRAWINGS IF NO DESIGNER OF RECORD IS SHOWN FOR THIS
 PROJECT. ELECTRICAL PERMIT REQUIRED
 4.SHOW PROPER SPACING AT THE KITCHEN LOCATION AND
 THROUGHOUT SCOPE. PER FBC RES E3901- WALL SPACE
 REQUIREMENTS AND COUNTERTOP WALL SPACE IN KITCHEN AREA.
 5.SHOW THE SMOKE DETECTORS LAYOUT PER FBC RES 314
 REQUIREMENTS
 6.NEW SLIDING GLASS DOOR, PLEASE CLARIFY IF THERE IS AN
 EXISTING SWITCH AND LIGHTING OUTLET TO COMPLY WITH FBC
 RES E3903, IF NOT SHOW ON DRAWINGS.
 7.TAMPER RESISTANT RECEPTACLES REQUIRED, PROVIDE A NOTE
 TO COMPLY. FBC RES E4002.14
 8.FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL FREE
 TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD YOU
 HAVE ANY QUESTIONS OR CONCERNS.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  