Plan Review Notes
Plan Review Notes For Permit 16030744
Permit Number 16030744
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-03-31 14:24:09I HAVE REVIEWED PERMIT REVISION #16030744 (ORIGINAL
 PERMIT #15120638) AND AM READY TO PASS IN THE SYSTEM. I
 LOOKED AT THE UPDATED PERMIT VALUE AND SEE THAT THIS
 VALUE IS STILL TOO LOW AS IT DOES NOT INCLUDE 2 - 10"
 BACKFLOW PREVENTERS OR LARGER FIRE FEED MAIN PIPING.
 FOR INSTANCE, THE PLANS SHOW BOTH A 12-INCH FIRE (EAST)
 AND 10-INCH FIRE (WEST) SUPPLY FEEDING THE 8" FIRE
 LOOP. THE COST BREAK DOWN PROVIDED ON PAGE 112
 INDICATES THE 8" PVC FIRE MAIN BUT APPEARS TO EXCLUDE
 THE FOLLOWING:
  
 LINE ITEM 90 10" $36,970
 LINE ITEM 91 12" $16,965
 LINE ITEM 92 6" $20,492
 LINE ITEM 104 10" BACKFLOWS $29,612
 LINE ITEM 107 6" FDC $3,642