Plan Review Notes For Permit 16030744 |
Permit Number |
16030744 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-31 14:24:09 | I HAVE REVIEWED PERMIT REVISION #16030744 (ORIGINAL | | PERMIT #15120638) AND AM READY TO PASS IN THE SYSTEM. I | | LOOKED AT THE UPDATED PERMIT VALUE AND SEE THAT THIS | | VALUE IS STILL TOO LOW AS IT DOES NOT INCLUDE 2 - 10" | | BACKFLOW PREVENTERS OR LARGER FIRE FEED MAIN PIPING. | | FOR INSTANCE, THE PLANS SHOW BOTH A 12-INCH FIRE (EAST) | | AND 10-INCH FIRE (WEST) SUPPLY FEEDING THE 8" FIRE | | LOOP. THE COST BREAK DOWN PROVIDED ON PAGE 112 | | INDICATES THE 8" PVC FIRE MAIN BUT APPEARS TO EXCLUDE | | THE FOLLOWING: | | | | LINE ITEM 90 10" $36,970 | | LINE ITEM 91 12" $16,965 | | LINE ITEM 92 6" $20,492 | | LINE ITEM 104 10" BACKFLOWS $29,612 | | LINE ITEM 107 6" FDC $3,642 |
|