Plan Review Notes
Plan Review Notes For Permit 16030654
Permit Number 16030654
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-15 16:09:19THIS CUSTOMER CALLED ME ON THE PHONE ASKING WHAT HE
 WOULD NEED FOR THIS PERMIT AND I CLEARLY TOLD HIM WHAT
 I WANTED:
 1. A SITE PLAN SHOWING THE LOCATION OF THE SERVICE ON
 THE HOUSE. (I WAS LED TO BELIEVE THAT HE HAD PURCHASED
 TWO SFR NOT A MULTI-DWELLING UNIT.
 2. A SITE SPECIFIC RISER DIAGRAM, SHOWING CONDUCTOR
 SIZING, OVER CURRENT PROTECTION AND PROPER GROUNDING
 PER NEC 250.66
 3. SCOPE OF WORK SHALL BE DEFINED ON THE DRAWING AND
 JOB ADDRESS.
 4. THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DRAWING SHALL BE ON THE DRAWING
 ON THE OTHER HAND, IF THIS IS A MULTI-DWELLING UNIT, IT
 IS NOW A COMMERCIAL INSTALLATION AND THEREFORE IN
 ADDITION TO THE ABOVE,
 1. INDIVIDUAL UNIT LOAD CALCS TO VERIFY PROPER SERVICE
 SIZING.
 2. EVERY METER SOCKET SHALL BE MARKED WITH THE NUMBER
 OF THE UNIT IT SERVES.