Plan Review Notes
Plan Review Notes For Permit 16030643
Permit Number 16030643
Review Stop M
Sequence Number 1
Notes
Date Text
2016-04-14 16:11:56PROVIDE AHRI AT JOBSITE FOR INSPECTOR TO VERIFY
 EQUIPMENT.
  
 M1503.4 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE PROVIDED
 WITH MAKEUP AIR AT A RATE APPROXIMATELY EQUAL TO THE
 EXHAUST AIR RATE. SUCH MAKEUP AIR SYSTEMS SHALL BE
 EQUIPPED WITH A MEANS OF CLOSURE AND SHALL BE
 AUTOMATICALLY CONTROLLED TO START AND OPERATE
 SIMULTANEOUSLY WITH THE EXHAUST SYSTEM.
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved