2016-03-16 16:36:04THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 THE SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE.
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS REQUIRE AN
 EVALUATION BY A FIRE SPRINKLER CONTRACTOR.
  
 2. IF EXISTING, THE FIRE ALARM SYSTEM SHALL REMAIN
 ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD.
  
 3. ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
  
 4. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEM,
 EXCEEDS 4 HOURS, A FIRE WATCH SHALL BE IMPLEMENTED AND
 MAINTAINED UNTIL FULL AND COMPLETE PROTECTION IS
 RETURNED.
  
  