Plan Review Notes For Permit 16030582 |
Permit Number |
16030582 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-16 16:36:04 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | 1. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF | | THE SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE. | | ANY REMOVAL AND/OR CONSTRUCTION OF WALLS REQUIRE AN | | EVALUATION BY A FIRE SPRINKLER CONTRACTOR. | | | | 2. IF EXISTING, THE FIRE ALARM SYSTEM SHALL REMAIN | | ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD. | | | | 3. ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE | | DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE | | SAFETY CONTRACTORS. | | | | 4. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEM, | | EXCEEDS 4 HOURS, A FIRE WATCH SHALL BE IMPLEMENTED AND | | MAINTAINED UNTIL FULL AND COMPLETE PROTECTION IS | | RETURNED. | | | | |
|