2016-03-18 18:49:25 | RESIDENTIAL (R2) FLOORING ALTERATION. BUILDING REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- SOUND INSULATION MATERIAL SUBMITTED: |
| A) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS |
| (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS |
| REQUIRED BY SEC. 1207.2 OF FBC 5TH EDITION (2014). |
| NOTE: TEST SAMPLE TO MATCH ACTUAL BUILDING |
| CONSTRUCTION. INFORMATION SUBMITTED IS FOR 8" CONCRETE |
| SLAB WITH SUSPENDED ACOUSTICAL CEILING. THERE IS NOT |
| SUSPENDED ACOUSTICAL CEILING IN THIS BUILDING. |
| |
| B) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS |
| (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS |
| REQUIRED BY SEC. 1207.3 OF FBC 5TH EDITION (2014). |
| NOTE: TEST SAMPLE TO MATCH ACTUAL BUILDING |
| CONSTRUCTION. INFORMATION SUBMITTED IS FOR 8" CONCRETE |
| SLAB WITH SUSPENDED ACOUSTICAL CEILING. THERE IS NOT |
| SUSPENDED ACOUSTICAL CEILING IN THIS BUILDING. . |
| |
| C) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE |
| DEVELOPED TEST DONE IN ACCORDANCE WITH ASTM E 84 OR UL |
| 723 AS REQUIRED BY SEC. 720.1 OF FBC 5TH EDITION |
| (2014). |
| NOTE: TEST SAMPLE TO MATCH PROPOSED INSTALLATION. |
| |
| |