Plan Review Notes For Permit 16030533 |
Permit Number |
16030533 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-16 07:35:51 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. PLEASE SHOW THAT THE NEW DOOR LOCATION ON SCOPE HAS | | A MEANS OF ILLUMINATION AS YOU EXIT TO EXTERIOR. SHOW | | FIXTURE OUTLET PER NEC 210.70A2B | | 2. SHOW ON PLANS IF THERE ARE EXISTING SMOKE DETECTORS | | PER FBC RES 314, IF NOT SHOW ON PLANS. | | 3. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | THIS PROJECT. | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | | | |
|