2016-03-21 15:28:531ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030508
 3/21/16
  
 1) THE SUMMARY AC CALCULATIONS REQUIRE AN ENGINEERS
 SIGNATURE AND SEAL PER SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION. PLEASE CLARIFY WHY THERE IS NO
 VENTILATION AIR FOR OCCUPANTS SHOWN ON THE CALCS.
 2) PROVIDE A DOOR SCHEDULE THAT INDICATES THE TYPE OF
 AND SIZE OF LOUVERED DOORS AT THE AC CLOSETS- REFER TO
 SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION.
 3) THE CORRIDOR (HALLWAY 206) CANNOT SERVE AS A RETURN
 AIR DUCT FOR AHU-2- SEE SECTION 601.2 FBC-14
 MECHANICAL.
 4) THE AC SCHEDULE INDICATES A TOTAL OF 1600 CFM'S OF
 SUPPLY AIR FOR AHU-2, HOWEVER THE PLAN SHOWS A TOTAL OF
 1795 CFM'S BEING DISTRIBUTED IN THE ZONE.
 5) ALL NEW DUCT SMOKE DETECTORS SHALL BE INSTALLED IN
 THE RETURN AIR SYSTEMS OF THE AIR HANDLERS PER SECTION
 606.2.1 FBC-14 MECHANICAL.
  