2016-03-22 12:56:20 | 1ST ELECTRICAL REVIEW NOTES FOR REVISION #:16030508 |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 |
| NFPA 70 2011 (NEC) |
| |
| CORRECTIONS REQUIRED: |
| SHEET E0.1 |
| 1. DEMOLITION NOTES 10 HAVE UNDEFINED CODE QUOTED. SEE |
| CURRENT ADOPTED APPLICABLE CODE WHICH MAY NOT |
| NECESSARILY BE THE LATEST EDITIONS. |
| 2. SHEET E1.1 ELECTRICAL POWER PLAN IS MISSING. PLEASE |
| PROVIDE THIS SHEET FOR REVIEW. PLEASE NOTE THAT THE |
| FAILURE TO INCLUDE THIS SHEET IN THE INITIAL SUBMITTAL |
| MAY CREATE THE NEED FOR A SECOND RESUBMITTAL AS THIS |
| PAGE IS REVIEWED. |
| SHEET E2.1 |
| 1. IN ADDITION TO THE LIGHTING CONTROLLED MENTIONED. |
| COMPLIANCE W/FBC-EC405.2.2.3 DAYLIGHT ZONES SHALL BE |
| CONTROLLED SEPARATELY. |
| 2. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| CONDITIONED & UNCONDITIONED SPACES. |
| SHEET E3.1 |
| 1. NEC 110.16 ARC-FLASH HAZARD WARNING LABELS REQUIRED |
| ON ALL ELECTRICAL APPARATUS. |
| 2. NEC 110.24 MAXIMUM AVAILABLE FAULT CURRENT SHALL BE |
| DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS. |
| 3. NEC 408.4(B) ALL SWITCHBOARDS AND PANELBOARDS |
| SUPPLIED BY A FEEDER IN OTHER THAN A ONE OR TWO FAMILY |
| DWELLING SHALL BE MARKED TO INDICATE THE LOCATION AND |
| TYPE OF THE SOURCE OF POWER. |
| SHEET E5.1 |
| 1. INCLUDE THE PROPOSED FIRE STOPPING DETAIL FOR |
| ELECTRICAL OUTLET BOX IN A RATED WALL. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |