2016-03-21 10:45:23 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16030508 |
| ADD: 477 S. ROSEMARY SUITE # 230 |
| CONT: TBD |
| TEL: 684-6844/ NIKI BENNETT |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. MARCH 21/2016 |
| ACTION: DENIED |
| |
| 1) PLEASE REVIEW SHEET 004_A1.0 CORRIDOR 206 AND SHEET |
| 16044_M1_1. PLEASE REVIEW 2014 FBC-B 1018.5 AIR |
| MOVEMENT IN CORRIDORS. CORRIDORS SHALL NOT SERVE AS |
| SUPPLY, RETURN, EXHAUST, RELIEF OR VENTILATION AIR |
| DUCTS. THE MECHANICAL PLANS SHOW THE RETURN AIR IS |
| BEING PULLED DOWN THRU THE CEILING ABOVE INTO THE |
| CORRIDOR AND INTO THE AIR HANDLER CLOSET 209. THE DOOR |
| SCHEDULE INDICATES THIS DOOR IS A WOOD LOUVERED DOOR. |
| THE 2014 FBC-M DOES NOT ALLOW COMBUSTIBLE MATERIALS |
| WITHIN PLENUMS. THE SAME ISSUE WITH DOOR 224B, NO |
| COMBUSTIBLES ALLOWED WITHIN PLENUMS. |
| |
| NOTE FBC-B 1018.5 EXC. # 3 IS FOR OFFICES LESS THAN |
| 1,000 SQ. FT. |
| |