Plan Review Notes
Plan Review Notes For Permit 16030508
Permit Number 16030508
Review Stop B
Sequence Number 1
Notes
Date Text
2016-03-21 10:45:23BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030508
 ADD: 477 S. ROSEMARY SUITE # 230
 CONT: TBD
 TEL: 684-6844/ NIKI BENNETT
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MARCH 21/2016
 ACTION: DENIED
  
 1) PLEASE REVIEW SHEET 004_A1.0 CORRIDOR 206 AND SHEET
 16044_M1_1. PLEASE REVIEW 2014 FBC-B 1018.5 AIR
 MOVEMENT IN CORRIDORS. CORRIDORS SHALL NOT SERVE AS
 SUPPLY, RETURN, EXHAUST, RELIEF OR VENTILATION AIR
 DUCTS. THE MECHANICAL PLANS SHOW THE RETURN AIR IS
 BEING PULLED DOWN THRU THE CEILING ABOVE INTO THE
 CORRIDOR AND INTO THE AIR HANDLER CLOSET 209. THE DOOR
 SCHEDULE INDICATES THIS DOOR IS A WOOD LOUVERED DOOR.
 THE 2014 FBC-M DOES NOT ALLOW COMBUSTIBLE MATERIALS
 WITHIN PLENUMS. THE SAME ISSUE WITH DOOR 224B, NO
 COMBUSTIBLES ALLOWED WITHIN PLENUMS.
  
 NOTE FBC-B 1018.5 EXC. # 3 IS FOR OFFICES LESS THAN
 1,000 SQ. FT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  