2016-03-25 09:35:37BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030503
 ADD: 1451 OLIVE AVE.
 CONT: GILBANE
 TEL: 561-236-7052
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MARCH 25/2016
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES UNDER THE HEADING
 DESCRIPTION OF WORK: DEMOLITION OF A PORTION OF THE
 MUSEUM IN PREPARATION FOR EXPANSION. PLEASE INDICATE AS
 TO WHICH STAGE (SHEET 0003_D002_PHASING DIAGRAM) THIS
 SCOPE OF WORK THIS PERMIT PERTAINS TOO? IT APPEARS TO
 BE THE STAGE 4? 107.2.1.3. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2) SHEET 0004_LSD101 (LEVEL 1) INDICATES A TEMPORARY
 2ND EXIT FROM THE KING GALLERY ROOM A105.
 SHEET 0022_D351 SHOWS THE ROOMS A103 & B145 THE
 INFORMATION DESK AND INFORMATION ROOMS BEING DEMOLISHED
 AND SHEET 0004_LSD LEVEL 1 SHOWS A TEMPORARY 2 HR.
 WALL. THERE IS NO DOORWAY LEADING TO THE EXTERIOR.
 SHEET 0039_D801 DOES SHOW A EGRESS CORRIDOR AND EXIT
 PASSAGEWAY TO THE EXIT.
  
 2A) SHEET 0039_D801. THE PLANS DO NOT INDICATE HOW HIGH
 THE DECK IS ABOVE THE FLOOR LEVEL ? WHAT TYPE OF DECK
 DOES THIS FIRE RATED ASSEMBLY FASTEN TOO? IS IT A FIXED
 ASSEMBLY OR DOES IT HAVE A B DECK TYPE BOTTOM ASSEMBLY?
 PLEASE PROVIDE DETAILS? EXIT PASSAGEWAYS SHALL BE BUILT
 AS FIRE BARRIERS IN ACCORDANCE WITH 2014 FBC-B707.
  
 2B) SHEET 0039_D801. DETAIL #5 SHOWS A NEW EXTERIOR
 OPENING BUT THERE IS NO INFORMATION OF HOW THIS OPENING
 HAS BEEN CREATED, FILLED CELL BLOCK WITH REBAR, HEADER,
 LINTEL, WIND DESIGN, NO BUILDING CRITERIA PROVIDE?
 107.3.5.1.1. MINIMUM CRITERIA FOR COMMERCIAL PLAN
 REVIEW. PART OF THE MWFRS (MAIN WIND FORCE RESISTING
 SYSTEM).
  
 2D) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 2E) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 2F) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 3) SHEET 0004_LSD101. THIS SHEET INDICATES BRINGING IN
 PORTABLE RESTROOMS? WILL THEY BE USED ONSITE MORE THAN
 6 MONTHS. A SEPARATE PERMIT WILL BE REQUIRED, TIE
 DOWNS, ACCESSIBLE RAMP AND STAIRS, ACCESSIBLE
 RESTROOMS, HANDRAIL/ GUARDRAIL SYSTEMS AS WELL. 2014
 ADMIN. CODE 105.1.
  
 4) ON QUITE A FEW OF THE VARIOUS SHEETS THERE IS
 GRAVESITE PROTOCOL BUT NOT SUPPLIED IN THESE DOCUMENTS
 HOW TO PROTECT. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  