2016-03-25 09:35:37 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16030503 |
| ADD: 1451 OLIVE AVE. |
| CONT: GILBANE |
| TEL: 561-236-7052 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. MARCH 25/2016 |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION INDICATES UNDER THE HEADING |
| DESCRIPTION OF WORK: DEMOLITION OF A PORTION OF THE |
| MUSEUM IN PREPARATION FOR EXPANSION. PLEASE INDICATE AS |
| TO WHICH STAGE (SHEET 0003_D002_PHASING DIAGRAM) THIS |
| SCOPE OF WORK THIS PERMIT PERTAINS TOO? IT APPEARS TO |
| BE THE STAGE 4? 107.2.1.3. ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 2) SHEET 0004_LSD101 (LEVEL 1) INDICATES A TEMPORARY |
| 2ND EXIT FROM THE KING GALLERY ROOM A105. |
| SHEET 0022_D351 SHOWS THE ROOMS A103 & B145 THE |
| INFORMATION DESK AND INFORMATION ROOMS BEING DEMOLISHED |
| AND SHEET 0004_LSD LEVEL 1 SHOWS A TEMPORARY 2 HR. |
| WALL. THERE IS NO DOORWAY LEADING TO THE EXTERIOR. |
| SHEET 0039_D801 DOES SHOW A EGRESS CORRIDOR AND EXIT |
| PASSAGEWAY TO THE EXIT. |
| |
| 2A) SHEET 0039_D801. THE PLANS DO NOT INDICATE HOW HIGH |
| THE DECK IS ABOVE THE FLOOR LEVEL ? WHAT TYPE OF DECK |
| DOES THIS FIRE RATED ASSEMBLY FASTEN TOO? IS IT A FIXED |
| ASSEMBLY OR DOES IT HAVE A B DECK TYPE BOTTOM ASSEMBLY? |
| PLEASE PROVIDE DETAILS? EXIT PASSAGEWAYS SHALL BE BUILT |
| AS FIRE BARRIERS IN ACCORDANCE WITH 2014 FBC-B707. |
| |
| 2B) SHEET 0039_D801. DETAIL #5 SHOWS A NEW EXTERIOR |
| OPENING BUT THERE IS NO INFORMATION OF HOW THIS OPENING |
| HAS BEEN CREATED, FILLED CELL BLOCK WITH REBAR, HEADER, |
| LINTEL, WIND DESIGN, NO BUILDING CRITERIA PROVIDE? |
| 107.3.5.1.1. MINIMUM CRITERIA FOR COMMERCIAL PLAN |
| REVIEW. PART OF THE MWFRS (MAIN WIND FORCE RESISTING |
| SYSTEM). |
| |
| 2D) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING |
| |
| 2E) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 |
| NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| |
| 2F) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| 3) SHEET 0004_LSD101. THIS SHEET INDICATES BRINGING IN |
| PORTABLE RESTROOMS? WILL THEY BE USED ONSITE MORE THAN |
| 6 MONTHS. A SEPARATE PERMIT WILL BE REQUIRED, TIE |
| DOWNS, ACCESSIBLE RAMP AND STAIRS, ACCESSIBLE |
| RESTROOMS, HANDRAIL/ GUARDRAIL SYSTEMS AS WELL. 2014 |
| ADMIN. CODE 105.1. |
| |
| 4) ON QUITE A FEW OF THE VARIOUS SHEETS THERE IS |
| GRAVESITE PROTOCOL BUT NOT SUPPLIED IN THESE DOCUMENTS |
| HOW TO PROTECT. 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |