2016-03-21 10:43:12REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - ELECTRIC RISER TO INCLUDE FEEDER/BRANCH CIRCUIT WIRE
 SIZES AND CONDUIT DETAIL FROM ROOFTOP PANEL A TO AC
 DISCONNECT WBA 107.3.5.3
  
 - PROVIDE PANEL SCHEDULE WITH DEMAND LOADS ,AIC RATINGS
 OF EQUIPMENT & OCPD TO VERIFY IF LOAD CAPACITY MATCHES
 NAMEPLATE OF ROOFTOP CONDENSER UNIT. NEC 215.5 ,
 110.9/10 , 440
  
 - ELECTRICAL SUB-PERMIT IS REQUIRED PLEASE MAKE A NOTE
 FOR ARC-FLASH HAZARD WARNING LABEL AND AVAILABLE FAULT
 CURRENT MARKINGS. NEC 110.16 , 110.24
  
 - ADJUSTMENT FACTORS WILL BE TAKEN INTO CONSIDERATION
 FOR ALL RACEWAYS EXPOSED TO DIRECT SUNLIGHT ON TOP OF
 ROOFTOPS ACCORDING TO NEC TABLE 310.15 B3. A NOTE WILL
 SUFFICE.
  
 - PROVIDE A SERVICE RECEPTACLE GFCI PROTECTED WITHIN 25
 FT OR WITHIN SIGHT OF MECHANICAL EQUIPMENT. NEC 210.63
 , 210.8 B