2016-03-22 09:02:59 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16030431 |
| ADD: 1200 S. FLAGLER DR./ ROOF TOP EQUIPMENT |
| CONT: HILL YORK SERVICES |
| TEL: 561-689-7355 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. MARCH 22/ 2016 |
| ACTION: DENIED |
| |
| 1) SHEET S1 THE GENERAL DESIGN NOTE # 5 INDICATES THE |
| CONTRACTOR TO ATTACH THE NEW ROOF TOP UNIT PER THE |
| MANUFACTURERS SPECIFICATION. THE MANUFACTUTURERS |
| SPECIFICATION FOR THE ATTACHMENT OF THE NEW ROOF TOP |
| UNIT HAD NOT SUBMITTED ANY CALCULATIONS FOR THE |
| ATTACHMENT OF THE NEW UNIT TO THE |
| ELEVATED STEEL STAND. PLEASE SHOW COMPLIANCE WITH: |
| |
| 2014 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON |
| STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE |
| DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE |
| INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC |
| COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL |
| PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST |
| THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS? |
| |
| 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2) THE ENGINEERING CALCULATIONS FOR THE ATTACHMENT |
| METHOD OF THE NEW ROOF TOP UNIT TO THE STEEL STAND BY A |
| DELEGATE ENGINEER WILL NEED TO BE REVIEWED BY THE |
| STRUCTURAL ENGINEER OF RECORD, VICTOR G. GARAYCOCHEA |
| P.E., APPROVED AND SHOP DRAWING STAMP OF APPROVAL, |
| BEFORE THE SUBMITTAL CAN BE SUBMITTED TO THE BUILDING |
| DEPARTMENT. |
| |
| 3) IF THERE IS TO BE ANY FIELD WIELDING COMPLETED ON |
| SITE, CERTIFICATES WILL BE REQUIRED FOR THE |
| QUALIFICATIONS OF A CERTIFIED WIELDER WILL ALSO BE |
| REQUIRED. |
| |
| 4) JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |