Plan Review Notes
Plan Review Notes For Permit 16030431
Permit Number 16030431
Review Stop B
Sequence Number 1
Notes
Date Text
2016-03-22 09:02:59BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030431
 ADD: 1200 S. FLAGLER DR./ ROOF TOP EQUIPMENT
 CONT: HILL YORK SERVICES
 TEL: 561-689-7355
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 22/ 2016
 ACTION: DENIED
  
 1) SHEET S1 THE GENERAL DESIGN NOTE # 5 INDICATES THE
 CONTRACTOR TO ATTACH THE NEW ROOF TOP UNIT PER THE
 MANUFACTURERS SPECIFICATION. THE MANUFACTUTURERS
 SPECIFICATION FOR THE ATTACHMENT OF THE NEW ROOF TOP
 UNIT HAD NOT SUBMITTED ANY CALCULATIONS FOR THE
 ATTACHMENT OF THE NEW UNIT TO THE
 ELEVATED STEEL STAND. PLEASE SHOW COMPLIANCE WITH:
  
 2014 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON
 STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE
 DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE
 INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC
 COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL
 PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST
 THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2) THE ENGINEERING CALCULATIONS FOR THE ATTACHMENT
 METHOD OF THE NEW ROOF TOP UNIT TO THE STEEL STAND BY A
 DELEGATE ENGINEER WILL NEED TO BE REVIEWED BY THE
 STRUCTURAL ENGINEER OF RECORD, VICTOR G. GARAYCOCHEA
 P.E., APPROVED AND SHOP DRAWING STAMP OF APPROVAL,
 BEFORE THE SUBMITTAL CAN BE SUBMITTED TO THE BUILDING
 DEPARTMENT.
  
 3) IF THERE IS TO BE ANY FIELD WIELDING COMPLETED ON
 SITE, CERTIFICATES WILL BE REQUIRED FOR THE
 QUALIFICATIONS OF A CERTIFIED WIELDER WILL ALSO BE
 REQUIRED.
  
 4) JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  