2016-03-10 14:09:50RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS.
 CODE: FBC, 5TH EDITION (2014)
  
 1- SPECIFY ROOF PITCH, PITCHED ROOF AND FLAT ROOF
 SQUARE FOOTAGE AND MEAN ROOF HEIGHT AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS.
  
 2- FLAT ROOF PRODUCT APPROVAL:
 A) PROVIDE DRAWINGS THAT CORRESPOND TO FLORIDA PRODUCT
 APPROVAL FL10497-R5 SUBMITTED. DRAWINGS SUBMITTED ARE
 FOR FL10497-R3. THIS INFORMATION IS FOR REVISION #3.
 NEED TO PROVIDE CURRENT PRODUCT APPROVAL REVISION #5 AS
 REQUIRED BY
 FAC 61G20-3.002(33).
  
 B) CLEARLY MARK WHICH APPROVED ASSEMBLY FROM FLORIDA
 PRODUCT APPROVAL FL10497-R5 SUBMITTED IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). IF THE SELECTED ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND
 SEALED RAS 117 CALCULATIONS WILL BE REQUIRED.
  