2016-03-17 07:05:381ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION
 PERMIT #16030393
 3/17/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING AND
 PROVIDE MINIMUM VENTILATION CALCULATIONS PER TABLE
 403.3 FBC-14 MECHANICAL.
 2) INDICATE THE SIZE OF THE O/A DUCTS AND PROVIDE
 MOTORIZED DAMPERS AT EACH AIR HANDLER LOCATION- SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER