Plan Review Notes For Permit 16030393 |
Permit Number |
16030393 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-17 07:05:38 | 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING, | | ENERGY CONSERVATION | | PERMIT #16030393 | | 3/17/16 | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING AND | | PROVIDE MINIMUM VENTILATION CALCULATIONS PER TABLE | | 403.3 FBC-14 MECHANICAL. | | 2) INDICATE THE SIZE OF THE O/A DUCTS AND PROVIDE | | MOTORIZED DAMPERS AT EACH AIR HANDLER LOCATION- SECTION | | C403.2.4.4 FBC-14 ENERGY CONSERVATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|