2016-03-15 14:56:451ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030381
 3/15/16
  
 1) PROVIDE AN EXHAUST VENTILATION CALCULATION FOR EF-1.
 2) PROVIDE THE WIND LOAD DESIGN CRITERIA AND
 ENGINEERING FOR INSTALLATION OF THE ROOF MOUNTED FAN
 AND CURB. PROVIDE A SECTION CUT INDICATING THE TYPE,
 SIZE, AND AMOUNT OF FASTENERS FOR ANCHORING THE CURB TO
 THE STRUCTURE, AND THE FAN TO THE CURB.
  