Plan Review Notes
Plan Review Notes For Permit 16030375
Permit Number 16030375
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-10 19:16:17REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - NEC 250.32 A BUILDINGS OR STRUCTURES SUPPLIED BY
 FEEDERS OR BRANCH CIRCUITS SHALL HAVE A GROUNDING
 ELECTRODE.
  
 - NEC 680.21 C GFCI PROTECTION REQUIRED FOR POOL
 EQUIPMENT AND POOL PUMPS. ( NO POOL SPECS ON REAR LIKE
 STATED ON REVISION APPLICATION. )
  
 - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT,
 SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET
 SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE
 SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED WITHIN 25 FT. OF THE EQUIPMENT.
  
 -FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
  
 - NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES
  
 - NEC 110.26 HEIGHT OF WORKING CLEARNACE MAKE SURE
 PANEL UNDER STAIRS MEETS 6FT REQUIREMENT.
  
 - NEC 210.70 LIGHTING OUTLET REQUIRED IN STAIRS ( 3 WAY
 ) AND ALSO BASEMENT.
2016-03-10 09:27:18GAVE TO M. ALBARRAN