2016-06-15 15:30:48REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 -THE FOLLOWING ARE THE ELECTRICAL REQUIREMENTS THAT
 APPLY TO THE INTERIOR STAIRWAY MEANS OF EGRESS
  
 - 1006.1 ILLUMINATION REQUIRED. 1006.2 ILLUMINATION
 LEVEL.
 THE MEANS OF EGRESS, INCLUDING THE EXIT DISCHARGE,
 SHALL BE ILLUMINATED AT ALL TIMES THE BUILDING SPACE
 SERVED BY THE MEANS OF EGRESS IS OCCUPIED.
 THE MEANS OF EGRESS ILLUMINATION LEVEL SHALL NOT BE
 LESS THAN 1 FOOTCANDLE (11 LUX) AT THE WALKING SURFACE.
  
 - FBC-B 1011. EXIT SIGNAGE REQUIRED.THE FACE OF AN EXIT
 SIGN ILLUMINATED FROM AN EXTERNAL SOURCE SHALL HAVE AN
 INTENSITY OF NOT LESS THAN 5 FOOTCANDLES
  
 - NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL BE
 FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT.
  
 - 1022.5 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH INTERIOR EXIT
 STAIRWAYS AND RAMPSARE PROHIBITED EXCEPT FOR REQUIRED
 EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR
 INDEPENDENT VENTILATION OR PRESSURIZATION, SPRINKLER
 PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR FIRE
 DEPARTMENT COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY
 SERVING THE INTERIOR EXIT STAIRWAY AND RAMP AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE PROTECTED
 IN ACCORDANCE WITH SECTION 714. THERE SHALL BE NO
 PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT INTERIOR EXIT
 STAIRWAYS AND RAMPS. OPEN PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 714.3.2.
  
  