Plan Review Notes For Permit 16030363 |
Permit Number |
16030363 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-16 14:52:16 | 1ST REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | 1. SHOW LOCATION OF WATER HEATER PAN DRAIN TERMINATION | | ON SANITARY RISER IT IS SHOWN ON WATER RISER | | TERMINATING INTO HUB DRAIN PLEASE CLARIFY. | | PER WPB AMEND. TO FBC 107.2.1 | | 2. PLEASE INDICATE MOUNTING HEIGHT OF GRAB BARS FROM | | TOP OF GRIPPING SURFACE.PER FBC ACC. SEC. 609.4 | | 3. SHOW TOILET 16-18" OFF SIDE WALL TO COMPLY WITH FBC | | ACC SEC. 604.2 | | 4. PROVIDE BACKFLOW PROTECTION FOR ICE MAKERS. | | PER FBC PL SEC. 608.3 |
|