2016-03-15 11:07:251ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16060363
 3/15/16
  
 1) PLEASE CLARIFY HOW AIR FORM OFFICE 103 & 104 IS
 BEING RETURNED TO AHU-6.
 2) THE TRANSFER DUCTS FROM OFFICES 106, 107, 116, 120,
 121, 123, & 124 ARE UNDERSIZED PER SECTION 601.5 FBC-14
 MECHANICAL: TRANSFERS MUST BE SIZED 1.5 TIMES THE
 CROSS-SECTIONAL AREA OF THE SUPPLY DUCT.
  