Plan Review Notes
Plan Review Notes For Permit 16030363
Permit Number 16030363
Review Stop IMPACT
Sequence Number 1
Notes
Date Text
2016-03-14 12:05:33BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030363
 ADD: 901 NORTHPOINT PKWY. SUITE 105-107
 CONT: CUTTING EDGE BUILDING SYSTEMS, INC.
 TEL: 561-625-4545
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MARCH 14/ 2016
 ACTION: DENIED
  
 1) SHEET A-1 NOTE F INDICATES THIS EXTERIOR WALL TO BE
 INFILLED. SHEET A2 DETAIL # 2 INDICATES A EXTERIOR
 OPENING IS TO BE INFILLED WITH BLOCK:
  
 1A) THERE IS A NOTE WITHIN THEBLOCK WALL INFILE THERE
 IS TO ALSO BE 8X8 INCH GLASS BLOCK. PLEASE NOT THERE
 HAS BEEN NO PRODUCT APPROVALS BUSMITTED FOR THIS
 NEWWINDOW OPENING. 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(B)
 WINDOWS.
  
 1B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 1C) IN THE DETAIL THERE IS A NOTE ABOUT 3 CONCRETE
 POURS. THE PLANS DO NOT INDICATE IF THESE ARE TO BE
 INFILE REINFORCED COLOUMN BLOCK, NOR DOES THE PLANS
 INDICATE THE SIZE OF THE REINFORCING BARS NOR DOES THE
 PLANS INDICATE HOW FAR INTO THE CONCRETE THE
 RE-INFORCING BARS ARE TO BE ENBEDDED. THE PLANS ARE
 ALSO DEFICIENT AS TO THE TYPE OF ADHESIVE TO BE USED ON
 THE REINFORCED REBARS. THIS WALL SECTION IS TO BECOME
 PART OF THE MWFRS (MAIN WIND FORCE RESISTING SYSTEM).
 2107.2.1 LAP SPLICES.
  
 1D) THE PLANS ARE ALSO DEFICIENT NOT GIVING HOW OFTEN
 HORIZONTAL JOINT RE-INFORCEMENT IS TO BE PLACED IN THE
 MASONRY WALL. ACI 530 / 12.7.4.
  
 2A) SHEET A-1 DOOR 16 IS TO BE REPLACED. SHEET A-2 THE
 DOOR SCHEDULE, DOOR # 16 INDICATES THE CONTRACTOR TO
 SUBMIT PRODUCT APPROVAL FOR THE REPLACED DOOR. 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
  
 2B )107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 2C) THE PLANS DO NOT PROVIDE THE WIND DESIGN CRITERIA
 FOR THE NEW OPENINGS. 2014 FBC-B 1603.1.4 WIND DESIGN
 DATA. THE FOLLOWING INFORMATION RELATED TO WIND LOADS
 SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN
 THE DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2. RISK CATEGORY.
  
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3) NEITHER A1 NOR THE LS1 SHEET SHOW ELEVATIONS OF THE
 BREAK ROOM. THE ELECTRICAL SHEETS DO INDICATE THERE IS
 AN ELECTRICAL CIRCUIT FOR A MICROWAVE, PLEASE SHOW
 COMPLIANCE WITH : 2014 FBC-ACCESSIBILITY CODE:
  
 308.2.2 FOWARD. OBSTRUCTED HIGH REACH. WHERE A HIGH
 FORWARD REACH IS OVER AN OBSTRUCTION, THE CLEAR FLOOR
 SPACE SHALL EXTEND BENEATH THE ELEMENT FOR A DISTANCE
 NOT LESS THAN THE REQUIRED REACH DEPTH OVER THE
 OBSTRUCTION. THE HIGH FORWARD REACH SHALL BE 48 INCHES
 (1220 MM) MAXIMUM WHERE THE REACH DEPTH IS 20 INCHES
 (510 MM) MAXIMUM. WHERE THE REACH DEPTH EXCEEDS 20
 INCHES (510 MM), THE HIGH FORWARD REACH SHALL BE 44
 INCHES (1120 MM) MAXIMUM AND THE REACH DEPTH SHALL BE
 25 INCHES (635 MM) MAXIMUM.
  
 308.3.2 SIDE. OBSTRUCTED HIGH REACH. WHERE A CLEAR
 FLOOR OR GROUND SPACE ALLOWS A PARALLEL APPROACH TO AN
 ELEMENT AND THE HIGH SIDE REACH IS OVER AN OBSTRUCTION,
 THE HEIGHT OF THE OBSTRUCTION SHALL BE 34 INCHES (865
 MM) MAXIMUM AND THE DEPTH OF THE OBSTRUCTION SHALL BE
 24 INCHES (610 MM) MAXIMUM. THE HIGH SIDE REACH SHALL
 BE 48 INCHES (1220 MM) MAXIMUM FOR A REACH DEPTH OF 10
 INCHES (255 MM) MAXIMUM. WHERE THE REACH DEPTH EXCEEDS
 10 INCHES (255 MM), THE HIGH SIDE REACH SHALL BE 46
 INCHES (1170 MM) MAXIMUM FOR A REACH DEPTH OF 24 INCHES
 (610 MM) MAXIMUM.
  
 309 OPERABLE PARTS
 309.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL
 BE PROVIDED.
  
 309.3 HEIGHT.
 OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR MORE OF
 THE REACH RANGES SPECIFIED IN 308.
  
 4) JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  