Plan Review Notes
Plan Review Notes For Permit 16030363
Permit Number 16030363
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-14 07:54:55INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE CLARIFY THE RISER DIAGRAM SHOWS SERVICE
 CONDUCTORS ROUTED TO FPL TRANSFORMER AND NOT TAPED IN
 EXISTING GUTTER. IF THE TAP OCCURS IN THE GUTTER PLEASE
 SHOW AS SUCH AND DELETE ONE LINE STRAIGHT TO
 TRANSFORMER. FBC 107.3.5
 2. ADD A NOTE TO RISER DIAGRAM TO INDICATE NEC 110.16
 ARC-FLASH WARNING LABELS REQUIRED AND NEC 110.24
 REQUIREMENTS AVAILABLE FAULT CURRENTS. A NOTE WILL
 SUFFICE.
 3. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL
 FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE
 ANY QUESTIONS OR CONCERNS.
  