Plan Review Notes For Permit 16030363 |
Permit Number |
16030363 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-03-14 07:54:55 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. PLEASE CLARIFY THE RISER DIAGRAM SHOWS SERVICE | | CONDUCTORS ROUTED TO FPL TRANSFORMER AND NOT TAPED IN | | EXISTING GUTTER. IF THE TAP OCCURS IN THE GUTTER PLEASE | | SHOW AS SUCH AND DELETE ONE LINE STRAIGHT TO | | TRANSFORMER. FBC 107.3.5 | | 2. ADD A NOTE TO RISER DIAGRAM TO INDICATE NEC 110.16 | | ARC-FLASH WARNING LABELS REQUIRED AND NEC 110.24 | | REQUIREMENTS AVAILABLE FAULT CURRENTS. A NOTE WILL | | SUFFICE. | | 3. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL | | FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE | | ANY QUESTIONS OR CONCERNS. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | | | |
|