2016-11-28 14:45:28 | RESIDENTIAL (R3) ADDITION/ALTERATION SIXTH BUILDING |
| REVIEW CHECKLIST. |
| CODE: FBC-5TH EDITION (2014). |
| |
| NOTE: |
| THE PERMIT CAN NOT BE ISSUED WITHOUT THE ENERGY |
| CALCULATIONS. |
| SEC. R103.1.1.2 FBC-ENERGY CONSERVATION |
| |
| |
| |
| 1- REVISE ENERGY CALCULATIONS SUBMITTED: |
| A)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| FORM, INCLUDING CORRECT OWNER'S NAME, BUILDER NAME, |
| PERMIT OFFICE AND JURISDICTION NUMBER. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| RESPONSE: |
| REPEAT COMMENT. NEEDS BUILDER NAME, PERMIT OFFICE AND |
| JURISDICTION NUMBER. |
| |
| B) SEC. R806.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014) |
| REQUIRES 1/150 ATTIC VENTILATION RATIO. ATTIC |
| INFORMATION ON PAGE 2 OF 4 SPECIFIES 1/300 ATTIC |
| VENTILATION RATIO. PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS SHOWING HOW THIS HOUSE COMPLIES WITH THE |
| EXCEPTION OF SEC. R806.2 FOR 1/300 ATTIC VENTILATION |
| RATIO. OTHERWISE REVISE AS REQUIRED. |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED AT ALL. SEE ARCHITECTURAL |
| PLANS. THEY CALL FOR 1/150 RATIO NOT 1/300. REVISE AS |
| REQUIRED. |
| |
| C) COMPLETE THE INSPECTION CHECKLIST AS REQUIRED BY |
| SEC. R405.4.2 FBC-ENERGY CONSERVATION. |
| RESPONSE: |
| INSPECTION CHECKLIST NEED TO BE COMPLETED. CHECKLIST |
| NEED TO BE CHECKED WITH THE ITEMS THAT APPLY. |
| |
| D) PROVIDE THE NAME OF THE INDIVIDUAL COMPLETING THE |
| ENERGY CALCULATIONS AS REQUIRED BY SEC. R405.4.2 |
| FBC-ENERGY CONSERVATION. |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED AT ALL. THE NAME OF THE |
| PERSON COMPLETING THE ENERGY CALCULATIONS WAS NOT |
| PROVIDED. ONLY A COPY OF A SIGNATURE WAS PROVIDED. |
| PROVIDE THE COMPLETE NAME OF THE PERSON COMPLETING THE |
| CALCULATIONS. |
| |
| NOTE: LABEL FOR WINDOWS AND DOORS U-FACTOR AND SHGC |
| FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL BE |
| REQUIRED FOR VERIFICATION. |
| |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |