Date |
Text |
2016-10-26 10:55:37 | 10/26/16 TALKED TO RICHARD BARNES (ARCH.) TO GO OVER |
| COMMENTS (# OF PEOPLE , A/C SIZING, A/C SEER). |
| |
| 10/26/16 TALKED TO TONY PIEDRA (CONTRACTOR) TO GO OVER |
| COMMENTS AND PROVISO. HE SAID HE'LL RESUBMIT ALONG WITH |
| LANDSCAPE REQUEST. |
| |
| |
| RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC-5TH EDITION (2014). |
| |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS THAT CONTRACTOR MAY SUBMIT REQUESTED INFORMATION |
| AFTER THE PERMIT IS ISSUED AND BEFORE INSPECTIONS TO |
| AVOID CONFLICTS/DELAYS. REVISION FEES MAY APPLY. |
| CONTRACTOR TO ADVICE IF RESUBMITTING INFORMATION NOW OR |
| IF PROVISO OPTION IS PREFERRED AT THIS TIME. |
| |
| 1- REVISE ENERGY CALCULATIONS SUBMITTED: |
| A) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| FORM, INCLUDING CORRECT OWNER'S NAME ("HOMEOWNER" IS |
| NOT AN OWNER), BUILDER NAME, PERMIT OFFICE AND |
| JURISDICTION NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| |
| B) REVISE NUMBER OF OCCUPANTS SHOWN UNDER "SPACES" ON |
| PAGE 2 OF 4. THIS IS A THREE BEDROOM HOUSE. CLARIFY WHY |
| CONSIDERING ONLY ONE OCCUPANT. THE NUMBER OF OCCUPANTS |
| MAY AFFECT THE A/C SIZING LOAD CALCULATIONS. A HIGH |
| NUMBER OF OCCUPANTS MAY RESULT TO OVERSIZE THE A/C |
| EQUIPMENT. ON THE OTHER HAND, A LOW NUMBER OF OCCUPANTS |
| MAY RESULT TO UNDERSIZE THE A/C EQUIPMENT. PROVIDE THE |
| COMPLETE A/C LOAD CALCULATIONS (NOT JUST THE SUMMARY) |
| TO VERIFY EQUIPMENT SIZING. EQUIPMENT CAN NOT BE |
| OVERSIZED OR UNDERSIZED. SEE SEC. R403.6.1 AND SEC. |
| R403.6.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| TYPICALLY A THREE BEDROOM HOUSE IS OCCUPIED BY MORE |
| THAN ONE PERSON. THE PURPOSE OF THE ENERGY CALCULATIONS |
| AND EQUIPMENT SIZING IS TO CONTRIBUTE TO THE ENERGY |
| CONSERVATION BY PROPERLY DESIGNING THE STRUCTURE AND |
| THE EQUIPMENT TO BE USED. IF ONLY USING ONE PERSON FOR |
| THE DESIGN PARAMETERS, THEN PROVIDE COMPLETE |
| DOCUMENTATION SUPPORTING THIS DESIGN APPROACH. |
| DOCUMENTATION WILL BE FORWARDED TO THE BUILDING |
| OFFICIAL FOR REVIEW AND APPROVAL. |
| |
| C) SEC. R806.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014) |
| REQUIRES 1/150 ATTIC VENTILATION RATIO. ATTIC |
| INFORMATION ON PAGE 2 OF 4 SPECIFIES 1/300 ATTIC |
| VENTILATION RATIO. PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS SHOWING HOW THIS HOUSE COMPLIES WITH THE |
| EXCEPTION OF SEC. R806.2 FOR 1/300 ATTIC VENTILATION |
| RATIO. OTHERWISE REVISE AS REQUIRED. |
| |
| D) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION TO |
| MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, |
| 5TH EDITION (2014). |
| |
| E) MISSING THE INSPECTION CHECKLIST AS REQUIRED BY SEC. |
| R405.4.2 FBC-ENERGY CONSERVATION. |
| |
| F) PROVIDE THE NAME OF THE INDIVIDUAL COMPLETING THE |
| ENERGY CALCULATIONS AS REQUIRED BY SEC. R405.4.2 |
| FBC-ENERGY CONSERVATION. |
| |
| G) BUILDER TO COMPLETE AND PROVIDE THE EPL DISPLAY |
| CARD. SEC. R405.4.2 FBC-ENERGY CONSERVATION. |
| |
| NEW COMMENT: |
| H) ITEM #12 SPECIFIES 18 SEER FOR THE COOLING |
| EQUIPMENT. FLOOR PLAN M-1 SPECIFIES 15 SEER. REVISE AS |
| REQUIRED TO MATCH. SEC. R103.2 FBC-ENERGY CONSERVATION. |
| |
| NOTE: LABEL FOR WINDOWS AND DOORS U-FACTOR AND SHGC |
| FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL BE |
| REQUIRED FOR VERIFICATION. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. DON'T |
| STAPLE OLD DRAWINGS. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| (561)805-6712 |
| [email protected] |
| |
| 10/26/16 TALKED TO RICHARD BARNES (ARCH.) TO GO OVER |
| COMMENTS (# OF PEOPLE , A/C SIZING, A/C SEER). |
| |
| 10/26/16 TALKED TO TONY PIEDRA (CONTRACTOR) TO GO OVER |
| COMMENTS AND PROVISO. HE SAID HE'LL RESUBMIT ALONG WITH |
| LANDSCAPE REQUEST. |