2016-10-03 11:52:23RESIDENTIAL (R3) ADDITION/ALTERATION THIRD BUILDING
 REVIEW CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR MAY SUBMIT REQUESTED INFORMATION
 AFTER THE PERMIT IS ISSUED AND BEFORE INSPECTIONS TO
 AVOID CONFLICTS/DELAYS. REVISION FEES MAY APPLY.
 CONTRACTOR TO ADVICE IF RESUBMITTING INFORMATION NOW OR
 IF PROVISO OPTION IS PREFERRED AT THIS TIME.
  
  
  
 ORIGINAL COMMENT:
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 RESPONSE:
 ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM, INCLUDING CORRECT OWNER'S NAME ("HOMEOWNER" IS
 NOT AN OWNER), BUILDER NAME, PERMIT OFFICE AND
 JURISDICTION NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) REVISE NUMBER OF OCCUPANTS SHOWN UNDER "SPACES" ON
 PAGE 2 OF 4. THIS IS A THREE BEDROOM HOUSE. PROVIDE
 PROOF OF WHY CONSIDERING ONLY ONE OCCUPANT. (THE NUMBER
 OF OCCUPANTS MAY AFFECT THE A/C SIZING LOAD
 CALCULATIONS). SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 C) SEC. R806.2 OF FBC-RESIDENTIAL, 5TH EDITION (2014)
 REQUIRES 1/150 ATTIC VENTILATION RATIO. ATTIC
 INFORMATION ON PAGE 2 OF 4 SPECIFIES 1/300 ATTIC
 VENTILATION RATIO. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THIS HOUSE COMPLIES WITH THE
 EXCEPTION OF SEC. R806.2 FOR 1/300 ATTIC VENTILATION
 RATIO. OTHERWISE REVISE AS REQUIRED.
  
 D) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 E) MISSING THE INSPECTION CHECKLIST AS REQUIRED BY SEC.
 R405.4.2 FBC-ENERGY CONSERVATION.
  
 F) PROVIDE THE NAME OF THE INDIVIDUAL COMPLETING THE
 ENERGY CALCULATIONS AS REQUIRED BY SEC. R405.4.2
 FBC-ENERGY CONSERVATION.
  
 G) BUILDER TO COMPLETE AND PROVIDE THE EPL DISPLAY
 CARD. SEC. R405.4.2 FBC-ENERGY CONSERVATION.
  
 NOTE: LABEL FOR WINDOWS AND DOORS U-FACTOR AND SHGC
 FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL BE
 REQUIRED FOR VERIFICATION.
  
 ORIGINAL COMMENT:
 2- SITE PLAN FOOTPRINT SUBMITTED DOESN'T MATCH PROPOSED
 FLOOR PLAN ON SHEET A-5. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 REVISE SITE PLAN: THE DRAWING IS NOT CLEAR. THE
 ADDITION WAS BLOCKED BY A DARK BACKGROUND. DRAWING IS
 NOT LEGIBLE. SEC. 107.2.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE. DON'T
 STAPLE OLD DRAWINGS.
  